All heat pumps with a Smart Grid contact (2 contacts provided on 90% of all new heat pumps) can be controlled with Luqas. We tested the following:
Brand | Type | Connection relay 1 | Connexion relay 2 |
Alpha Innotec | SW H3 • SWC(V) H1/H3 • WZS(V) H3 • PWZS(V) H1/H2/H3 | IN5 | IN6 |
LWCV • LWDV • LW(A)V • LW(A)HV • LWAV+ • Paros • LWP | IN3 | IN4 | |
Atlantic | Alféa Extensa A.I. | EX1 on X11 looped through to L-5 via LQS relay | EX2 on X11 looped through to L-5 via LQS relay |
Alféa Excellia A.I. | EX1 on X11 looped through to L-5 via LQS relay | EX2 on X11 looped through to L-5 via LQS relay | |
Bosch | All heat pumps | I1 | I4 |
Buderus | All heat pumps | I1 | I4 |
Bulex | GeniaAir Tek HA x-7.2 | S21 | X41/FB + 0(ꓕ) |
GeniaAir Mono HA x-6 | S21 | X41/FB + 0(ꓕ) | |
GeniaAir Split HA x-5 | S21 | X41/FB + 0(ꓕ) | |
CTC | All heat pumps | K25 (Smart A) | K26 (Smart B) |
Daikin | Altherma 2 CB series(1) | LAN adapter: X1A/1+2 | LAN adapter: X1A/3+4 |
Altherma 3 D-series (1) | LAN adapter: X1A/1+2 | LAN adapter: X1A/3+4 | |
Altherma 3 E-series | X5M/9+10 | X5M/5+6 | |
Hitachi | Yutaki, Yutampo and Hisense Hi-Therma models | SG ready Input 1 | SG ready Input 2 |
Itho Daalderop | HP-S | K2 | ES |
LG | Therma V Lucht/Water | TB_SG1 | TB_SG2 |
Midea | M Thermal Arctic | SG contact | EVU contact |
Swan 2 | SG contact | EVU contact | |
Mitsubishi | Ecodan C-series generatie R2 | TBI.3 IN11 | TBI.3 IN12 |
Ecodan D-series | TBI.3 IN11 | TBI.3 IN12 | |
Ecodan E-series | TBI.3 IN11 | TBI.3 IN12 | |
Nibe | All heat pumps | Connecting and assigning to AUX contact | Connecting and assigning to AUX contact |
Thermastage | Thermastage Compact 05-11 | EX1 | EX2 |
Thermastage Compact 13-16 | EX1 | EX2 | |
Thermia | Atlas | BM card: D21 (408) or EM3 card D95 (408) | BM card D22 (409) or EM3 card D96 (409) |
Calibra | BM card: D21 (408) or EM3 card D95 (408) | BM card D22 (409) or EM3 card D96 (409) | |
Mega | BM card: D21 (408) or EM3 card D95 (408) | BM card D22 (409) or EM3 card D96 (409) | |
Athena | BM card: D21 (408) or EM3 card D95 (408) | BM card D22 (409) or EM3 card D96 (409) | |
Vaillant | aroTHERM pure /7.2 (uniTOWER /7.2) | S21 | X41/FB + 0(ꓕ) |
aroTHERM plus /6 (uniTOWER VIH /6 / VWZ MEH 97) | S21 | X41/FB + 0(ꓕ) | |
Weishaupt | WWP WEM / WWP T300 A / WWP WPM | SGR1 – input H1 | SGR2 – input H2 |
LAN adapter module required (version BRP069A61)
This list is not exhaustive. Other Smart Grid-ready heat pumps can be found at https://www.waermepumpe.de/normen-technik/sg-ready-datenbank/.
We are happy to help you! Marc, Stan, Nico, Maarten, Dieter and Maarten (VP).